The Siemens SENTRON 3VA5110-1MU36-0AA0 is a 3-pole molded-case circuit breaker, part of the 3VA5 UL frame 125 series, specifically designed for starter protection applications. It operates with a rated insulation voltage of 800V and a rated operating voltage of 690V AC.
This circuit breaker features an operational current of 100A at 40°C, with derated values at higher temperatures up to 70°C. Its short-circuit protection is managed by the TM120M overcurrent release, with an adjustable setting current (Ii) ranging from 3 to 7 times the nominal current.
Key electrical performance includes a maximum breaking capacity (Icu) of 150kA at 240V and 70kA at 415V, and an operating short-circuit current (Ics) of 150kA at 240V and 70kA at 415V. The short-circuit making capacity (Icm) is 330kA at 240V and 154kA at 415V.
Designed for DIN rail mounting, this circuit breaker has a mechanical service life of typically 20,000 switching cycles and an electrical endurance of up to 8,000 cycles at 380/415V AC-1. It is UL 489 listed as HACR Type and has a net weight of 1.034 kg.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operating voltage for this circuit breaker at AC is 690 V.
The operational current at 40°C is 100 A.
The breaking capacity (Icu) at 240V is 150 kA.
The adjustable setting current (Ii) for I-tripping ranges from 3 to 7 times the nominal current (In).
The mounting type is DIN Rail.