| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Current Rating (Amps) | |
| Front Connection | |
| Height | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating |
This Siemens 3VA5110-1BB22-0AA0 is a molded-case circuit breaker designed for reliable circuit protection. It features a 2-pole configuration and a robust construction suitable for various industrial applications.
The breaker has an operational current rating of 100A at temperatures up to 60°C, with derating at higher temperatures. Its rated insulation voltage is 600V, and the maximum operational voltage for DC is 250V, while the rated operational voltage for AC is 415V.
With a mechanical service life of 20,000 switching cycles and electrical endurance ratings of 8,000 cycles at 380/415V AC, this circuit breaker is built for durability. It is designed for front connection with a nut keeper kit and supports conductor cross-sections up to 17 x 6.5 mm. The unit mounts on a DIN rail for easy installation.
Key technical data includes a maximum power loss of 12.8W and an active power loss of 6.4W per pole under rated conditions. The breaker is designated as HACR Type according to UL 489 standards.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated operational voltage for AC is 415 V.
The operational current is 100 A at temperatures up to 60°C.
This is a 2-pole circuit breaker.
The mounting type is DIN Rail.
The RoHS status is RoHS3 Compliant.
The Moisture Sensitivity Level is 1 Unlimited.
The REACH status is REACH Unaffected.