This Siemens 3RV27111ED10 is a size S00 circuit breaker, suitable for system protection according to UL 489 and CSA C22.2 No. 5 standards. It offers a rated operational current of 4A and a maximum operating voltage of 690V.
The circuit breaker utilizes a thermal magnetic trip design for overload and short-circuit protection, with an instantaneous trip response value of 52A. It has a breaking capacity of up to 100 kA at 400V.
Designed for DIN rail mounting, this component features a rotary actuator and a mechanical and electrical endurance of typically 100,000 switching cycles. The operating ambient temperature range is -20 to +60 °C.
Key specifications include a 3-pole configuration, 690V insulation voltage, and standard compliance with CE, CSA, EAC, UL489, and VDE.
20 to 690 V AC.
-20 to +60 °C.
Up to 100 kA at 400 V AC (Icu).
CE, CSA, EAC, UL489, VDE.
Yes, it includes an auxiliary switch.
100,000 switching cycles for main and auxiliary contacts.
4 A.