| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Operating Temperature | |
| Storage Temperature | |
| Voltage | |
| Voltage Rating |
This Siemens 3RV24111EA10 is a S00 size circuit breaker, specifically designed for transformer protection applications. It operates with a thermal magnetic trip mechanism and offers an adjustable current response value ranging from 2.8 to 4 Amperes.
The circuit breaker is rated for a maximum operating voltage of 690V and a maximum operating frequency of 50-60 Hz. It has a rated operational current of 4A at 400V for both AC-3 and AC-3e applications. The device provides a breaking capacity of up to 100 kA at 240-500V and 6 kA at 690V for Icu, and up to 100 kA at 240-500V and 4 kA at 690V for Ics.
Key protective functions include phase failure detection, with a trip class of CLASS 10. The circuit breaker is designed for DIN rail mounting and features a rotary actuator. It has a mechanical and electrical endurance of typically 100,000 switching cycles. The operating temperature range is -20 to +60 °C.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The adjustable current response value for the current-dependent overload release is 2.8 to 4 A.
The rated operating voltage is 20 to 690 V, with a maximum of 690 V for AC-3 and AC-3e.
This circuit breaker has 3 poles for the main current circuit.
The trip class is CLASS 10.
The operating temperature range is -20 to +60 °C.