| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Relative Humidity | |
| Voltage | |
| Voltage Rating |
This Siemens 3RV24111DA10 circuit breaker is part of the SIRIUS 3RV2 series, designed for transformer protection applications. It is a size S00 breaker with three poles and a DIN rail mounting type.
The breaker utilizes a thermal magnetic release for overload protection, with an adjustable current response value ranging from 2.2 to 3.2 Amperes. It has an operational current rating of 3.2 A at AC-3 and AC-3e at 400 V. The rated operating voltage is up to 690 V.
Key electrical protection features include phase failure detection and a trip class of CLASS 10. The breaking capacity (Icu and Ics) at 240V and 400V is 100 kA, and at 690V it is 10 kA. The instantaneous short-circuit trip unit has a response value of 65 A.
Environmental conditions for operation include an ambient temperature range of -20 to +60 °C and a relative humidity of 10 to 95%. The device is suitable for installation at altitudes up to 2000 meters.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The adjustable current response value for the current-dependent overload release is 2.2 to 3.2 A.
The rated operating voltage is up to 690 V.
This circuit breaker uses DIN rail mounting.
Yes, the RoHS status is RoHS3 Compliant.
The ambient temperature during operation is -20 to +60 °C.