| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Operating Temperature | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating |
This Siemens 3RV24110GA15 circuit breaker is specifically designed for transformer protection applications. It belongs to the SIRIUS product family and features a size S00 frame. The adjustable current response value for the overload release is set between 0.45 and 0.63 A, with a nominal release current of 13 A.
The breaker operates with a 3-pole main circuit and offers a rated operating voltage of up to 690 V AC. It provides a high breaking capacity of 100 kA at various voltage levels, including 240V, 400V, 500V, and 690V AC. The trip class is rated as Class 10, utilizing a thermal overload release mechanism.
Included with this model are transverse auxiliary switches, providing 1 normally open (NO) and 1 normally closed (NC) contact. These auxiliary contacts are rated for AC-15 at 24V (2A) and 120V/230V (0.5A), and DC-13 at 24V (1A).
The circuit breaker is designed for DIN rail mounting and operates within an ambient temperature range of -20 to +60 °C. It also features phase failure detection for enhanced protection.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The adjustable current response value for the current-dependent overload release is between 0.45 and 0.63 A.
The rated operating voltage is up to 690 V AC.
The breaking capacity (Icu) at AC at 240V, 400V, 500V, and 690V is 100 kA.
Yes, it includes transverse auxiliary switches with 1 normally open (NO) and 1 normally closed (NC) contact.
The operating temperature range is -20 to +60 °C.
The RoHS status is RoHS3 Compliant.
The Moisture Sensitivity Level is Level 1.