This Siemens 3RV24110DA10 is a thermal magnetic circuit breaker from the SIRIUS 3RV2 series, specifically designed for transformer protection applications. It features a size S00 and is suitable for DIN rail mounting.
The breaker has three poles and an adjustable current response value for overload protection ranging from 0.22 to 0.32 A. The instantaneous short-circuit trip unit responds at 6.5 A. It operates with a rated voltage of up to 690 V and a frequency of 50-60 Hz.
Key electrical characteristics include a maximum breaking capacity (Icu and Ics) of 100 kA at 400 V. The device also includes phase failure detection and has a trip class of CLASS 10. The power loss in hot operating state is 5.5 W, with 1.8 W per pole.
Environmental specifications include an operating temperature range of -20 to +60 °C and a maximum installation altitude of 2,000 m. The mechanical and electrical endurance for the main and auxiliary contacts is a typical 100,000 switching cycles.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The adjustable current response value for the current-dependent overload release is between 0.22 and 0.32 A.
The maximum operating voltage for this circuit breaker is 690 V.
The operating temperature range for this circuit breaker is -20 to +60 °C.
Yes, this circuit breaker is RoHS3 Compliant.