| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Relative Humidity | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage | |
| Voltage Rating |
This Siemens 3RV23324XC10 is a size S2 circuit breaker, specifically designed for use in starter combinations. It operates with a rated current of 59A and supports a maximum operating voltage of 690V across AC-3 and AC-3e applications.
The breaker offers robust protection with a breaking capacity (Icu) of up to 100 kA at 240V and 400V, and 6 kA at 690V. Its breaking capacity (Ics) is rated at 50 kA at 400V and 4 kA at 690V. The instantaneous short-circuit trip unit has a response value of 845A.
With a mechanical and electrical endurance of typically 20,000 switching cycles, this circuit breaker is built for reliability. It is suitable for DIN rail mounting and features a rotary actuator. The operating temperature range is -20°C to +60°C.
Key electrical specifications include power loss of 26W at AC in hot operating state, and it supports various motor horsepower ratings under UL/CSA standards, including 20 hp for 3-phase AC motors at 220/230V.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated current is 59 A.
The maximum operating voltage is 690 V.
It is designed for DIN rail mounting.
The ambient temperature during operation is -20 ... +60 °C.
The RoHS status is RoHS3 Compliant.