| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Relative Humidity | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage | |
| Voltage Rating |
This Siemens 3RV23314VC10 is a size S2 circuit breaker designed for starter combinations. It features a 45A operational current rating at 400V and a maximum operating voltage of 690V.
The breaker offers a breaking capacity (Icu) of 65 kA at 400V and 650A instantaneous trip current. It has a mechanical service life of 50,000 switching cycles for both main and auxiliary contacts, and an electrical endurance of 50,000 cycles.
With a power loss of 24.5W at AC in hot operating state, this circuit breaker operates within an ambient temperature range of -20°C to +60°C. It is mounted on a DIN rail and is suitable for various industrial applications requiring reliable circuit protection.
Key electrical specifications include a 3-pole configuration, 50/60 Hz operating frequency, and compliance with UL/CSA ratings for motor applications.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current rating is 45A.
The maximum operating voltage is 690V.
It has 3 poles for the main current circuit.
The breaking capacity (Icu) at AC at 400V is 65 kA.
The ambient temperature during operation is -20°C to +60°C.
It is designed for DIN rail mounting.