| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Relative Humidity | |
| Voltage | |
| Voltage Rating |
This Siemens 3RV23111JC10 circuit breaker, part of the SIRIUS 3RV2 series, is designed for starter combinations and offers a rated current of 10A. It operates with a 3-pole main current circuit and supports a wide operating voltage range from 20V to 690V, with a maximum rated voltage of 690V at AC-3 and AC-3e.
The breaker has a size S00 and is suitable for DIN rail mounting. It features a magnetic trip type and a rotary actuator. The power loss at AC in a hot operating state is 9.25W. It boasts a high mechanical and electrical endurance, with typical switching cycles of 100,000 for both main and auxiliary contacts.
Key electrical specifications include a breaking capacity of up to 100 kA at 240V and 400V. The instantaneous short-circuit trip unit has a response value of 130A. Ambient conditions for operation range from -20°C to +60°C.
The product is compliant with RoHS3 and has an MSL of 1. It is designed for reliable protection in various industrial applications.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated current for the Siemens 3RV23111JC10 circuit breaker is 10A at AC-3 and AC-3e at 400V.
The maximum rated operating voltage for the Siemens 3RV23111JC10 circuit breaker is 690V.
The Siemens 3RV23111JC10 circuit breaker has 3 poles for the main current circuit.
The operating ambient temperature range for the Siemens 3RV23111JC10 is -20°C to +60°C.
The breaking capacity (Icu) at AC at 400V is 100 kA, and the operating short-circuit current (Ics) at AC at 400V is also 100 kA.
The circuit breaker size is S00.