| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Storage Temperature | |
| Voltage | |
| Voltage Rating |
This Siemens 3RV20234DA10 is a motor protection circuit breaker designed for robust industrial applications. It features a size S0 form factor and a thermal magnetic breaker type.
The device provides a 3-pole configuration with an adjustable current response value for overload protection ranging from 18 to 25 A. It has a rated operational current of 25 A at 400 V (AC-3 and AC-3e) and can handle a maximum operating voltage of 690 V. The circuit breaker is equipped with a CLASS 10 trip class and a thermal overload release.
Key protective functions include phase failure detection. It offers a breaking capacity of 4 kA (Icu) and 2 kA (Ics) at 690 V. The instantaneous short-circuit trip unit responds at 325 A. UL/CSA ratings are also provided, including a full-load current of 25 A at 480 V and 600 V.
Mounting is facilitated via DIN rail. The operating ambient temperature range is -20 to +60 °C.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operating voltage range is 20 to 690 V.
The operational current rated value is 25 A.
The trip class is CLASS 10.
The operating ambient temperature range is -20 to +60 °C.
Yes, it features phase failure detection.
It is designed for DIN rail mounting.