3RV20214BA15 The Siemens 3RV20214BA15 is a 3-pole circuit breaker designed for motor protection. It offers a 20A operational current and a 690V AC voltage rating.
Mfr Part #:

3RV20214BA15

Mfr Name: Siemens
Siemens
The Siemens 3RV20214BA15 is a 3-pole circuit breaker designed for motor protection. It offers a 20A operational current and a 690V AC voltage rating.
Stock on Request

3RV20214BA15 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Approval Agency
Breaker Type
Current Rating (Amps)
Dimensions
Illumination
Mounting Type
Number of Poles
Relative Humidity
Voltage Rating

3RV20214BA15 Description

Short technical summary and product information.

The Siemens 3RV20214BA15 is a motor protection circuit breaker from the SIRIUS 3RV2 series. It is designed for robust protection with a thermal overload release and a trip class of CLASS 10. This S0 size breaker operates with a 3-pole main circuit and features a current-dependent overload release adjustable from 13 to 20 A.

 

Key electrical specifications include a rated operational current of 20 A at 400V AC (AC-3 and AC-3e), and a maximum operating voltage of 690V AC. It provides a breaking capacity of 100 kA at 240V AC and 55 kA at 400V AC. The breaker also includes auxiliary contacts, with 1 NO and 1 NC contact available for transverse switching.

 

Designed for easy installation, the 3RV20214BA15 features DIN rail mounting. It operates within an ambient temperature range of -20 to +60 °C and has a mechanical and electrical endurance of typically 100,000 switching cycles. The ATEX type of protection is Ex II (2) GD, with suitability certificate DMT 02 ATEX F 001.

3RV20214BA15 Quick Information

Product Type: Circuit Breaker
Series: 3RV2
Canonical Name: Siemens 3RV20214BA15 Circuit Breaker
Subcategory: Motor Protection Circuit Breaker

3RV20214BA15 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

3RV20214BA15 Features

  • Motor protection circuit breaker with thermal release.
  • Adjustable overload current from 13 to 20 A.
  • Rated for 690 V AC maximum operating voltage.
  • Features 1 NO and 1 NC auxiliary contacts.
  • DIN rail mountable for easy installation.

3RV20214BA15 Applications

  • Ideal for motor overload protection.
  • Suitable for industrial control panels.
  • Used in power distribution systems.
  • Applicable in hazardous environments (ATEX).

3RV20214BA15 FAQs

7 frequently asked questions generated from this part’s specifications.
What is the operating voltage range for this circuit breaker?

The rated operating voltage range is 20 to 690 V.

What is the ambient temperature range for operation?

The ambient temperature during operation is -20 to +60 °C.

What is the RoHS status of the Siemens 3RV20214BA15?

The RoHS status is RoHS3 Compliant.

What is the Moisture Sensitivity Level (MSL) for this part?

The Moisture Sensitivity Level (MSL) is 1 Unlimited.

What is the trip class of this circuit breaker?

The trip class is CLASS 10.

What is the maximum breaking capacity of the 3RV20214BA15?

The maximum breaking capacity (Icu) at AC at 240 V is 100 kA.

How many poles does this circuit breaker have?

This circuit breaker has 3 poles for the main current circuit.