3RV20114AA10 The Siemens 3RV20114AA10 is a 3-pole circuit breaker designed for motor protection. It offers a 16A operational current and a 690V voltage rating.
Mfr Part #:

3RV20114AA10

Mfr Name: Siemens
Siemens
The Siemens 3RV20114AA10 is a 3-pole circuit breaker designed for motor protection. It offers a 16A operational current and a 690V voltage rating.
Stock on Request

3RV20114AA10 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Approval Agency
Breaker Type
Current Rating
Current Rating (Amps)
Illumination
Mounting Type
Number of Poles
Operating Voltage
Voltage Rating

3RV20114AA10 Description

Short technical summary and product information.

The Siemens 3RV20114AA10 is a motor protection circuit breaker from the SIRIUS 3RV2 series. It features a size S00 frame and is designed for DIN rail mounting.

 

This 3-pole breaker has an adjustable current response value ranging from 10 to 16 A, with a rated operational current of 16 A at 400V AC-3 and AC-3e. It supports a wide operating voltage range from 20 to 690 V, with a maximum rated voltage of 690 V for AC-3 and AC-3e applications. The breaker provides phase failure detection and has a thermal overload release type with a CLASS 10 trip class.

 

Key electrical specifications include a breaking capacity (Icu) of up to 100 kA at 240 V AC and 55 kA at 400 V AC. The operating frequency is rated at 50-60 Hz. The breaker is suitable for use in environments with an installation altitude up to 2000 m and operates within an ambient temperature range of -20 to +60 °C.

 

It also meets ATEX directive requirements for use in potentially explosive atmospheres (Ex II (2) GD) with certificate DMT 02 ATEX F 001. The mechanical service life for both main and auxiliary contacts is a typical 100,000 switching cycles.

3RV20114AA10 Quick Information

Product Type: Circuit Breaker
Series: 3RV2
Canonical Name: Siemens 3RV20114AA10 Circuit Breaker
Subcategory: Motor Protection

3RV20114AA10 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

3RV20114AA10 Features

  • Motor protection circuit breaker for industrial use.
  • Adjustable thermal overload protection from 10-16A.
  • Rated for 690V AC operation with 3 poles.
  • DIN rail mounting for easy installation.
  • ATEX certified for explosive atmospheres.

3RV20114AA10 Applications

  • Ideal for motor control circuits.
  • Suitable for industrial automation systems.
  • Used in hazardous location installations.
  • Protects electrical equipment from overloads.

3RV20114AA10 FAQs

7 frequently asked questions generated from this part’s specifications.
What is the current rating of the Siemens 3RV20114AA10 circuit breaker?

The adjustable current response value for the overload release is 10 to 16 A, and the rated operational current is 16 A.

What is the maximum voltage rating for this circuit breaker?

The rated operating voltage is 20 to 690 V, with a maximum rated value of 690 V for AC-3 and AC-3e.

How many poles does the Siemens 3RV20114AA10 have?

This circuit breaker has 3 poles for the main current circuit.

What type of mounting is supported by this circuit breaker?

The Siemens 3RV20114AA10 circuit breaker supports DIN rail mounting.

What is the trip class of this circuit breaker?

The trip class for this circuit breaker is CLASS 10.

Does this circuit breaker offer phase failure detection?

Yes, this circuit breaker features phase failure detection.

What are the operating temperature limits for this device?

The operating ambient temperature range is -20 to +60 °C.