3RV20111KA15 The Siemens 3RV20111KA15 is a 3-pole circuit breaker designed for motor protection. It offers a current rating of 12.5A and a voltage rating of 690V.
Mfr Part #:

3RV20111KA15

Mfr Name: Siemens
Siemens
The Siemens 3RV20111KA15 is a 3-pole circuit breaker designed for motor protection. It offers a current rating of 12.5A and a voltage rating of 690V.
Stock on Request

3RV20111KA15 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Approval Agency
Breaker Type
Current Rating
Current Rating (Amps)
Illumination
Mounting Type
Number of Poles
Operating Temperature
Relative Humidity
Storage Temperature
Voltage Rating

3RV20111KA15 Description

Short technical summary and product information.

The Siemens 3RV20111KA15 is a size S00 circuit breaker specifically designed for motor protection applications. It features a thermal overload release with an adjustable current response value ranging from 9 to 12.5 A, ensuring reliable protection for motors.

 

This 3-pole breaker operates at a rated voltage of up to 690V and has an operational current rating of 12.5A at 400V (AC-3 and AC-3e). It provides a maximum short-circuit breaking capacity of 100 kA at 240V AC. The breaker includes auxiliary contacts, with 1 normally open (NO) and 1 normally closed (NC) contact, suitable for signaling and control circuits.

 

Designed for standard switching capacity, the 3RV20111KA15 is mounted on a DIN rail. It operates within an ambient temperature range of -20 to +60 °C and has a mechanical and electrical endurance of typically 100,000 switching cycles. The breaker is also certified according to ATEX directive 2014/34/EU for use in potentially explosive atmospheres.

3RV20111KA15 Quick Information

Product Type: Circuit Breaker
Series: 3RV2
Canonical Name: Siemens 3RV20111KA15 Circuit Breaker
Subcategory: Motor Protection Circuit Breaker

3RV20111KA15 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

3RV20111KA15 Features

  • Designed for motor protection applications.
  • Adjustable thermal overload release (9-12.5A).
  • 3-pole configuration with 690V rating.
  • Includes 1 NO and 1 NC auxiliary contacts.
  • DIN rail mounting for easy installation.

3RV20111KA15 Applications

  • Ideal for motor control circuits.
  • Suitable for industrial automation systems.
  • Used in power distribution panels.
  • Applicable in hazardous environments (ATEX).

3RV20111KA15 FAQs

6 frequently asked questions generated from this part’s specifications.
What is the operating voltage range of the 3RV20111KA15?

The operating voltage is rated from 20 V to 690 V AC, with a maximum of 690 V at AC-3 and AC-3e.

What mounting type does this motor starter protector use?

It is designed for DIN rail mounting.

What is the operating temperature range?

The ambient temperature during operation is -20 °C to +60 °C.

What is the adjustable current range of the overload release?

The adjustable current response value is 9 A to 12.5 A.

How many auxiliary contacts does it have and what are their ratings?

It has 1 normally open (NO) and 1 normally closed (NC) auxiliary contact. At AC-15, the NO/NC contacts are rated 2 A at 24 V and 0.5 A at 230 V. At DC-13, they are rated 1 A at 24 V and 0.15 A at 60 V.

Does the 3RV20111KA15 include phase failure detection?

Yes, it includes phase failure detection.