This Siemens 3RV20111GA100BA0 is a specialized circuit breaker from the SIRIUS 3RV2 series, engineered for robust motor protection. It features a size S00 form factor and a thermal magnetic overload release with an adjustable current response value ranging from 4.5 to 6.3 A. The breaker is designed for a rated operational voltage of up to 690 V and offers a high breaking capacity of 100 kA at 400 V.
With a trip class of CLASS 10 and phase failure detection capabilities, this circuit breaker ensures reliable protection against overcurrents and short circuits. It is suitable for operation in ambient temperatures from -50 to +60 °C and mounts conveniently on a DIN rail. The device also includes standard switching capacity and a mechanical service life of up to 500 switching cycles.
Key electrical characteristics include a rated operational current of 6.3 A and power ratings up to 2.2 kW at 400 V AC-3. The breaker is equipped with screw terminals for secure connections. Its design prioritizes safety and performance in industrial motor control applications.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The adjustable current response value for the current-dependent overload release is 4.5 to 6.3 A.
The rated operating voltage is 20 to 690 V, with a maximum rated value of 690 V at AC-3.
The breaking capacity (Icu) is 100 kA at 240V, 400V, and 500V, and 6 kA at 690V. The operating breaking capacity (Ics) is also 100 kA at 240V, 400V, and 500V, and 4 kA at 690V.
The circuit breaker can operate in ambient temperatures ranging from -50 to +60 °C.
Yes, the RoHS status is listed as RoHS3 Compliant.