3RV20111EA15 The Siemens 3RV20111EA15 is a 3-pole circuit breaker designed for motor protection. It features a thermal overload release with an adjustable current response of 2.8-4A and a rated operational current of 4A.
Mfr Part #:

3RV20111EA15

Mfr Name: Siemens
Siemens
The Siemens 3RV20111EA15 is a 3-pole circuit breaker designed for motor protection. It features a thermal overload release with an adjustable current response of 2.8-4A and a rated operational current of 4A.
Stock on Request

3RV20111EA15 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Ambient Temperature
Approval Agency
Breaker Type
Current Rating
Current Rating (Amps)
Illumination
Mounting Type
Number of Poles
Relative Humidity
Storage Temperature
Voltage Rating

3RV20111EA15 Description

Short technical summary and product information.

The Siemens 3RV20111EA15 is a motor protection circuit breaker from the SIRIUS 3RV2 series, size S00. It offers a thermal overload release with an adjustable current response range of 2.8 to 4 A and a rated operational current of 4 A at 400V.

 

This 3-pole circuit breaker operates at a rated voltage of up to 690 V and has a breaking capacity of 100 kA at 240 V. It includes transverse auxiliary switches with 1 normally closed (NC) and 1 normally open (NO) contact. The device is designed for DIN rail mounting and is suitable for applications requiring phase failure detection.

 

Environmental conditions for operation include an ambient temperature range of -20 to +60 °C and a maximum installation altitude of 2,000 meters. The circuit breaker has a mechanical and electrical endurance of typically 100,000 switching cycles.

3RV20111EA15 Quick Information

Product Type: Circuit Breaker
Series: 3RV2
Canonical Name: Siemens 3RV20111EA15 Circuit Breaker
Subcategory: Motor Protection Circuit Breaker

3RV20111EA15 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

3RV20111EA15 Features

  • Designed for motor protection applications.
  • Adjustable thermal overload release (2.8-4A).
  • Rated operational current of 4A at 400V.
  • Features 1 NO and 1 NC auxiliary contacts.
  • Suitable for DIN rail mounting.

3RV20111EA15 Applications

  • Motor circuit protection.
  • Industrial control panels.
  • Machine automation systems.
  • Power distribution units.

3RV20111EA15 FAQs

7 frequently asked questions generated from this part’s specifications.
What is the operating voltage range of the 3RV20111EA15?

The rated operating voltage is 20 to 690 V AC, with a maximum of 690 V at AC-3 and AC-3e.

What is the mounting type for this device?

The mounting type is DIN Rail.

What is the ambient operating temperature range?

The ambient temperature during operation is -20 to 60 °C.

What is the adjustable current range of the overload release?

The adjustable current response value is 2.8 to 4 A.

How many poles does the main current circuit have?

The device has 3 poles for the main current circuit.

Does the 3RV20111EA15 include auxiliary contacts?

Yes, it includes an auxiliary switch with 1 normally open (NO) and 1 normally closed (NC) contact.

What ATEX certification does this device hold?

It is certified Ex II (2) GD according to ATEX directive 2014/34/EU, with certificate DMT 02 ATEX F 001.