3RV20111CA20 The Siemens 3RV20111CA20 is a 3-pole circuit breaker designed for motor protection. It features a thermal overload release with an adjustable current response value of 1.8 to 2.5 A.
Mfr Part #:

3RV20111CA20

Mfr Name: Siemens
Siemens
The Siemens 3RV20111CA20 is a 3-pole circuit breaker designed for motor protection. It features a thermal overload release with an adjustable current response value of 1.8 to 2.5 A.
Stock on Request

3RV20111CA20 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Approval Agency
Breaker Type
Current Rating
Current Rating (Amps)
Illumination
Lead Style
Mounting Type
Number of Poles
Storage Temperature
Voltage Rating

3RV20111CA20 Description

Short technical summary and product information.

The Siemens 3RV20111CA20 is a motor protection circuit breaker from the SIRIUS 3RV2 series, size S00. It offers a thermal overload release with an adjustable current range of 1.8 to 2.5 A and a fixed N-release of 33 A. This 3-pole breaker is designed for operation at voltages up to 690 V and has a rated operational current of 2.5 A at 400 V.

 

Key electrical characteristics include a breaking capacity (Icu) of 100 kA at 240/400/500 V and 10 kA at 690 V. It also features phase failure detection and a CLASS 10 trip class. The breaker is suitable for mounting on a DIN rail.

 

Environmental conditions for operation include an ambient temperature range of -20 to +60 °C and relative humidity of 10 to 95%. The device has a mechanical and electrical endurance of typically 100,000 switching cycles. It is ATEX certified for use in hazardous environments.

3RV20111CA20 Quick Information

Product Type: Circuit Breaker
Series: 3RV2
Canonical Name: Siemens 3RV2011-1CA20 Circuit Breaker
Subcategory: Motor Protection Circuit Breaker

3RV20111CA20 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

3RV20111CA20 Features

  • Motor protection circuit breaker, size S00.
  • Adjustable thermal overload release: 1.8-2.5 A.
  • Rated for 690 V AC operation.
  • High breaking capacity: 100 kA at 400 V.
  • DIN rail mounting for easy installation.

3RV20111CA20 Applications

  • Ideal for motor circuit protection.
  • Suitable for industrial control panels.
  • Used in hazardous area applications (ATEX).
  • Provides overload and short-circuit protection.

3RV20111CA20 FAQs

7 frequently asked questions generated from this part’s specifications.
What is the adjustable current response range of the 3RV20111CA20?

The adjustable current response value is 1.8 to 2.5 A.

What is the rated operational current of the 3RV20111CA20?

The rated operational current is 2.5 A.

What is the operating voltage range of the 3RV20111CA20?

The operating voltage range is 20 to 690 V AC.

What is the breaking capacity of the 3RV20111CA20?

The breaking capacity (Icu/Ics) is 100 kA at 240 V, 400 V, and 500 V AC, and 10 kA at 690 V AC.

Does the 3RV20111CA20 have phase failure detection?

Yes, the 3RV20111CA20 has phase failure detection.

What is the trip class of the 3RV20111CA20?

The trip class is CLASS 10.

What is the operating temperature range of the 3RV20111CA20?

The operating ambient temperature range is -20 to +60 °C.