3RV20110JA10 The Siemens 3RV20110JA10 is a 3-pole circuit breaker designed for motor protection. It features a thermal overload release with an adjustable current range of 0.7 to 1 A and a rated operational current of 1 A.
Mfr Part #:

3RV20110JA10

Mfr Name: Siemens
Siemens
The Siemens 3RV20110JA10 is a 3-pole circuit breaker designed for motor protection. It features a thermal overload release with an adjustable current range of 0.7 to 1 A and a rated operational current of 1 A.
Stock on Request

3RV20110JA10 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Approval Agency
Breaker Type
Current Rating
Current Rating (Amps)
Illumination
Mounting Type
Number of Poles
SVHC Present
Voltage Rating

3RV20110JA10 Description

Short technical summary and product information.

The Siemens 3RV20110JA10 is a circuit breaker from the SIRIUS 3RV2 series, specifically designed for motor protection applications. This device is built with a size S00 frame and offers a 3-pole configuration.

 

Key electrical characteristics include a rated operational current of 1 A at AC-3 and AC-3e, with a maximum operating voltage of 690 V. The adjustable current response value for the overload release ranges from 0.7 A to 1 A, and it operates with a CLASS 10 trip class. The breaker provides a high breaking capacity, with a maximum short-circuit current (Icu) of 100 kA at various voltages up to 690 V.

 

This circuit breaker is suitable for installation on a DIN rail. It features phase failure detection and a thermal design for the overload release. The device also meets ATEX directive requirements for type of protection.

 

Additional technical data includes a mechanical service life of 100,000 switching cycles for both main and auxiliary contacts, and an electrical endurance of 100,000 cycles. Ambient operating temperatures range from -20 to +60 °C.

3RV20110JA10 Quick Information

Product Type: Circuit Breaker
Series: 3RV2
Canonical Name: Siemens 3RV2 Circuit Breaker, S00 Size, 1A Current Rating, 3 Poles, 690V Voltage Rating
Subcategory: Motor Protection Circuit Breaker

3RV20110JA10 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

3RV20110JA10 Features

  • Designed for motor protection applications.
  • Size S00, 3-pole circuit breaker.
  • 1A operational current rating.
  • Adjustable thermal overload release (0.7-1A).
  • DIN rail mounting type.

3RV20110JA10 Applications

  • Motor control circuits.
  • Industrial automation systems.
  • Machine protection.
  • Power distribution panels.

3RV20110JA10 FAQs

7 frequently asked questions generated from this part’s specifications.
What is the operating voltage range of the 3RV20110JA10?

The operating voltage range is 20 to 690 V AC.

What is the adjustable current range for overload protection?

The adjustable current response value is 0.7 to 1 A.

What is the breaking capacity of this motor starter protector?

The rated breaking capacity (Icu and Ics) is 100 kA at 240 V, 400 V, 500 V, and 690 V AC.

What mounting type does the 3RV20110JA10 use?

The device mounts on a DIN rail.

What is the operating temperature range for this unit?

The ambient temperature during operation is -20 to +60 °C.

Does the 3RV20110JA10 have built-in auxiliary contacts?

No, it has 0 normally closed, 0 normally open, and 0 changeover auxiliary contacts. An auxiliary switch extension is available as an option.

What is the trip class and overload release type?

The trip class is CLASS 10 and the overload release is thermal type.