3RV20110CA10 The Siemens 3RV20110CA10 is a 3-pole circuit breaker designed for motor protection. It features a thermal overload release with an adjustable current range of 0.18 to 0.25 A.
Mfr Part #:

3RV20110CA10

Mfr Name: Siemens
Siemens
The Siemens 3RV20110CA10 is a 3-pole circuit breaker designed for motor protection. It features a thermal overload release with an adjustable current range of 0.18 to 0.25 A.
Stock on Request

3RV20110CA10 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Approval Agency
Breaker Type
Current Rating
Current Rating (Amps)
Illumination
Mounting Type
Number of Poles
Relative Humidity
Voltage Rating

3RV20110CA10 Description

Short technical summary and product information.

The Siemens 3RV20110CA10 is a motor protection circuit breaker from the SIRIUS 3RV2 series. It is designed for robust protection with a thermal overload release and a fixed N-release of 3.3 A. The breaker operates with a 3-pole main current circuit and supports a wide operating voltage range from 20 to 690 V.

 

Key electrical specifications include a rated operational current of 0.25 A at AC-3 and AC-3e, with a maximum breaking capacity of 100 kA at various voltages up to 690 V. The trip class is CLASS 10, ensuring reliable protection for motors.

 

This circuit breaker is suitable for mounting on a DIN rail and operates within an ambient temperature range of -20 to +60 °C. It also meets ATEX directive requirements for use in potentially explosive atmospheres.

 

Additional features include phase failure detection and a mechanical service life of up to 100,000 switching cycles. The breaker is compatible with contactor sizes S00 and S0.

3RV20110CA10 Quick Information

Product Type: Circuit Breaker
Series: 3RV2
Canonical Name: Siemens 3RV20110CA10 Circuit Breaker
Subcategory: Motor Protection Circuit Breaker

3RV20110CA10 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

3RV20110CA10 Features

  • 3-pole circuit breaker for motor protection.
  • Adjustable thermal overload release (0.18-0.25 A).
  • High breaking capacity of 100 kA.
  • Rated for 690 V AC operation.
  • DIN rail mounting for easy installation.

3RV20110CA10 Applications

  • Motor protection in industrial applications.
  • Control panels and distribution systems.
  • Equipment requiring overload protection.
  • Use in potentially explosive atmospheres (ATEX).

3RV20110CA10 FAQs

7 frequently asked questions generated from this part’s specifications.
What is the adjustable overload current range?

The adjustable current response value for the current-dependent overload release is 0.18 to 0.25 A.

What is the breaking capacity of this circuit breaker?

The maximum short-circuit breaking capacity (Icu) is 100 kA at AC voltages from 240 V to 690 V. The operating short-circuit breaking capacity (Ics) is also 100 kA.

What are the operating temperature limits?

The ambient temperature during operation is -20 to +60 °C.

What is the rated operating voltage?

The rated operating voltage range is 20 to 690 V AC.

What approvals does this circuit breaker have?

It is approved by ATEX, CCC, CSA, EAC, IECEx, and UL.

What is the mounting type?

The mounting type is DIN Rail.

Does it have phase failure detection?

Yes, phase failure detection is included.

Home