| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Operating Temperature | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage | |
| Voltage Rating |
The Siemens 3RV10110BA15 is a robust circuit breaker from the SIRIUS 3RV1 series, specifically engineered for motor protection applications. This device is built with a size S00 frame and offers a 3-pole configuration, ensuring comprehensive protection for three-phase motors.
Key electrical characteristics include an adjustable current response value for overload protection ranging from 0.14 to 0.2 A, a thermal overload release, and a Class 10 trip class. It operates with a rated voltage of up to 690 V and has a breaking capacity of 100 kA at 400 V. The circuit breaker also includes a transverse auxiliary switch with 1 normally open (NO) and 1 normally closed (NC) contact for signaling purposes.
Designed for standard switching capacity, this circuit breaker mounts conveniently on a DIN rail. It operates within an ambient temperature range of -20 to +60 °C and has a mechanical and electrical endurance of typically 100,000 switching cycles. Compliance includes RoHS3, REACH Unaffected, and MSL 1.
This component is suitable for various industrial applications requiring reliable motor circuit protection, offering a balance of performance, safety, and durability.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The adjustable current response value for the current-dependent overload release is 0.14 to 0.2 A.
The rated operating voltage is 20 to 690 V, with a maximum at AC-3 and AC-3e of 690 V.
The trip class is CLASS 10.
The operating temperature range is -20 to +60 °C.
Yes, it includes phase failure detection.
This circuit breaker is designed for DIN Rail mounting.