This Siemens 3RV1011-1JA15 is a Size S00 circuit breaker from the SIRIUS 3RV1 series, specifically designed for motor protection applications. It offers a thermal magnetic overload release with an adjustable current response value between 7 and 10 A, and a rated operational current of 10 A at 400V.
The breaker operates with a rated voltage of up to 690 V and has a breaking capacity of up to 100 kA at 240 V. It includes a transverse auxiliary switch with 1 NO and 1 NC contact, suitable for various control and signaling functions.
With a trip class of CLASS 10, this circuit breaker ensures reliable protection against phase failures. It is designed for DIN rail mounting and has a mechanical and electrical endurance of typically 100,000 switching cycles. The operating temperature range is -20 to +60 °C.
Key electrical specifications include a power loss of 9.25 W at AC in hot operating state and a surge voltage resistance of 6 kV. The insulation voltage is rated at 690 V with a degree of pollution 3.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operational current rated value is 10 A.
The rated value for operating voltage is 20 to 690 V.
It uses a thermal overload release.
The trip class is CLASS 10.
Yes, it includes phase failure detection.
The operating temperature range is -20 to +60 °C.
It has 3 poles for the main current circuit.