| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Operating Temperature | |
| Package Quantity | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage | |
| Voltage Rating |
This Siemens 3RV1011-0JA15 is a thermal magnetic circuit breaker in size S00, specifically designed for motor protection applications. It features a 3-pole configuration and an adjustable current response value ranging from 0.7 to 1 A, with a nominal operational current of 1 A at 400V AC-3.
The circuit breaker operates at a rated voltage of up to 690 V and has a rated frequency of 50 to 60 Hz. It offers a breaking capacity of 100 kA at various voltages. The device includes a transverse auxiliary switch with one normally open (NO) and one normally closed (NC) contact.
Designed for DIN rail mounting, this circuit breaker has a mechanical and electrical endurance of 100,000 switching cycles. It operates within an ambient temperature range of -20 to +60 °C and has an installation altitude limit of 2000 m.
Key electrical characteristics include a CLASS 10 trip class and phase failure detection. The power loss at AC in hot operating state is 5.5 W. It is compliant with RoHS3 and has a Moisture Sensitivity Level (MSL) of 1.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The operating voltage range is 20 to 690 V.
The operational current rating is 1 A.
The trip class is CLASS 10.
The operating temperature range is -20 to +60 °C.
Yes, it features phase failure detection.
It is designed for DIN rail mounting.
It has 3 poles.