| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating (Amps) | |
| Illumination | |
| Industrial Grade | |
| Mounting Type | |
| Number of Poles | |
| SVHC Present | |
| Storage Temperature | |
| Voltage Rating |
The Siemens 3RV1011-0FA10 is a circuit breaker specifically designed for motor protection applications. It belongs to the 3RV1 series and comes in size S00, compatible with S00 contactors. This thermal overload release breaker offers an adjustable current response value ranging from 0.35 A to 0.5 A, with a fixed N-release of 6.5 A.
Key electrical specifications include a rated operating voltage of up to 690 V AC, with operational currents of 0.5 A at AC-3 and AC-3e ratings at 400 V. The breaker provides a breaking capacity (Icu and Ics) of 100 kA at various voltages up to 690 V.
Environmental and mechanical data include an operating ambient temperature range of -20 to +60 °C and a mechanical service life of 100,000 switching cycles for both main and auxiliary contacts. The device is suitable for DIN rail mounting.
Compliance certifications include ATEX, CCC, CSA, EAC, IECEx, and UL. The ATEX type of protection is Ex II (2) GD, with certificate DMT 02 ATEX F 001.
The 3RV1011-0FA10 operates from 20 to 690 V AC.
The ambient operating temperature is -20 to +60 °C.
It has a trip class of CLASS 10.
The rated breaking capacity (Icu and Ics) is 100 kA at 240 V, 400 V, 500 V, and 690 V AC.
Yes, the device includes phase failure detection.
It is approved by ATEX, CCC, CSA, EAC, IECEx, and UL.
It mounts on a DIN rail.