This Siemens 3RV1011-0BA10 circuit breaker is part of the SIRIUS 3RV1 series, specifically designed for motor protection applications. It offers a thermal magnetic overload release with an adjustable current response value between 0.14 and 0.2 A, and an instantaneous short-circuit trip unit response value of 2.6 A.
The breaker has a size S00 and a 3-pole configuration, suitable for combination with contactors of the same size. It operates with a rated voltage of up to 690 V and a frequency of 50-60 Hz. The power loss at AC in a hot operating state is 5.5 W.
Key protective features include phase failure detection and a CLASS 10 trip class. The breaking capacity (Icu and Ics) at various voltages up to 690 V is rated at 100 kA. This unit is designed for DIN rail mounting and has a mechanical service life of 100,000 switching cycles.
Environmental conditions for operation include an ambient temperature range of -20 to +60 °C and relative humidity of 10 to 95%. It is ATEX certified with protection type Ex II (2) GD.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The adjustable current response value for the overload release is between 0.14 and 0.2 A.
This circuit breaker has a CLASS 10 trip class.
The rated operating voltage is up to 690 V.
This circuit breaker is designed for DIN rail mounting.