| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Ambient Temperature | |
| Approval Agency | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Insulation Resistance | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating |
The E-T-A 3600-P10-SI-1A is a single-pole thermal magnetic circuit breaker approved to CBE standard EN 60934 (IEC 60934). It is designed for panel mounting and features a push-to-reset actuator.
Key electrical specifications include a voltage rating of 240 VAC (50/60 Hz) or 65 VDC, with UL ratings of 250 VAC and 65 VDC. The current rating range is 0.05 to 16 A for the 3600 series. It offers a typical life of 5,000 operations at 1x IN inductive and 2x IN resistive loads.
Environmental specifications include an operating ambient temperature range of -30 to +60 °C and an operating area degree of protection of IP40. The breaker has undergone vibration, shock, corrosion, and humidity testing according to IEC standards.
Typical applications for this circuit breaker include process control systems, instrumentation, communications systems, and rail vehicles. It is designed for plug-in mounting with specific E-T-A sockets or panel mounting using E-T-A clips.
The breaker operates at 240VAC nominally and supports up to 250VAC per UL standards. It also handles 65VDC.
The device functions reliably within an ambient temperature range of -30°C to +60°C.
The unit provides an interrupting capacity of 400A for currents between 2.5A and 16A, and 1,000A under UL 1077 standards.
The typical life expectancy is 5,000 operations when tested at rated current with inductive or resistive loads.
The breaker utilizes a push-to-reset actuator for manual resetting after a trip event.