| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Approval Agency | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Operating Temperature | |
| Storage Temperature | |
| Tape & Reel | |
| Voltage Rating |
The E-T-A 3120-F511-P7T1-W12DY3-10A is a thermal circuit breaker that combines ON/OFF switching with integral overcurrent protection, conforming to S-type TO CBE to EN/IEC 60934 standards. It utilizes a bimetal trip element and is suitable for overload protection of motors, pumps, transformers, and cables.
Key electrical specifications include a current rating of 10A and voltage ratings of 250 VAC and 50 VDC. The breaker type is thermal, and it features a rocker actuator for operation. It is designed for panel mounting.
This circuit breaker is also available as a switch-only version. Options and add-on modules such as illumination, water splash protection, auxiliary contacts, under-voltage trip, remote trip, and magnetic trip are available. Typical applications include medical and laboratory equipment, apparatus and machine construction, professional tools, household and garden appliances, office machines, and audio equipment.
The device operates within an ambient temperature range of -30 to 60 °C. It offers an interrupting capacity of 150A for single-pole and 250A for double-pole configurations at 2.5-20A. The operating area has a degree of protection of IP40, and the terminal area can achieve IP54 or IP66 with a water splash cover.
| Qty | Low | High |
|---|---|---|
| 1+ | $0.99 | $0.99 |
Estimated market price range - modelled values for guidance only, not live distributor offers.
The rated voltage is 250 VAC and 50 VDC.
The current rating is 10A.
It features a panel mounting type.
-30 to 60°C.
The device has an IP40 degree of protection.
The interrupting capacity is 5000A at 250VAC per UL 1077.