The Phoenix Contact 2800898 is a thermomagnetic device circuit breaker designed for reliable circuit protection. This 2-pole unit offers a rated current of 10A and supports a rated voltage of up to 277V AC or 80V DC.
Key features include a fast-blow (F1) tripping characteristic, a trip-free mechanism, and a rated short-circuit switching capacity of 400A at 240V AC. The device has a compact design with dimensions of 45mm height, 24.6mm width, and 52mm depth, suitable for mounting on a base element.
Environmental specifications include an operating ambient temperature range of -30°C to 60°C and a degree of protection of IP30 at the actuation area. The inflammable class is V0 according to UL 94. This circuit breaker is suitable for various industrial and commercial applications requiring robust overcurrent protection.
Additional technical data includes a rated surge voltage of 2.5 kV and an insulation resistance greater than 100 MΩ. The device is designed for a maximum of 6000 cycles at 240V AC/1x In.
The rated current is 10 A.
The rated voltage is 277 V AC.
The tripping characteristic is F1 (fast-blow).
It has 2 poles.
The operating ambient temperature is -30 °C to 60 °C.
The degree of protection is IP30.