2800887 The Phoenix Contact 2800887 is a 2-pole thermomagnetic device circuit breaker rated for 10A and 277V AC. It features an M1 tripping characteristic and 2 PDT contacts.
Mfr Part #:

2800887

Mfr Name: Phoenix Contact
Phoenix Contact
The Phoenix Contact 2800887 is a 2-pole thermomagnetic device circuit breaker rated for 10A and 277V AC. It features an M1 tripping characteristic and 2 PDT contacts.
Stock on Request

2800887 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Breaker Type
Color
Contacts
Current Rating (Amps)
Depth
Fuse Type
Height
Insulation Resistance
Mounting Type
Number of Poles
Number of Positions
Rated Voltage
Voltage Rating
Width

2800887 Description

Short technical summary and product information.

The Phoenix Contact 2800887 is a thermomagnetic device circuit breaker designed for reliable circuit protection. This 2-position breaker features a tripping characteristic of M1 (medium-blow) and includes 2 PDT contacts, making it suitable for various applications.

 

With a rated current of 10A and a rated voltage of 277V AC (UL 1077) or 240V AC (IEC 60934), this device offers robust protection. It also supports DC voltage ratings up to 80V. The breaker has a rated short-circuit switching capacity of 400A at 240V AC and 600A at 80V DC.

 

Constructed with an inflammable class V0 rating according to UL 94, the device ensures safety in operation. It has a degree of protection IP30 at the actuation area and is designed for mounting on a base element. The operating ambient temperature range is -30°C to 60°C, with storage and transport temperatures ranging from -40°C to 80°C.

 

Key electrical specifications include a rated surge voltage of 2.5 kV and a voltage drop of 0.13V at 1x In. The insulation resistance is greater than 100 MΩ at 500V DC. The device is built for durability, with a maximum of 6000 cycles at 240V AC/1x In.

2800887 Quick Information

Product Type: Circuit Breaker
Canonical Name: Phoenix Contact CB TM2 10A M1 P Thermomagnetic Device Circuit Breaker
Subcategory: Thermomagnetic

2800887 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

2800887 Features

  • 2-pole thermomagnetic circuit breaker.
  • 10A rated current, 277V AC voltage.
  • M1 tripping characteristic.
  • 2 PDT contacts.
  • IP30 protection at actuation area.

2800887 Applications

  • Provides reliable circuit protection.
  • Suitable for industrial applications.
  • Designed for base element mounting.
  • Offers robust overcurrent protection.

2800887 FAQs

7 frequently asked questions generated from this part’s specifications.
What is the rated voltage of the Phoenix Contact 2800887 circuit breaker?

The rated voltage is 277 V AC (UL 1077) and 80 V DC (IEC 60934 and UL 1077).

What is the operating temperature range of this circuit breaker?

-30°C to 60°C operating, -40°C to 80°C storage.

What are the dimensions and mounting type of this circuit breaker?

Width 24.6mm, height 45mm, depth 52mm. It mounts on a base element.

What is the tripping characteristic of this circuit breaker?

M1 (medium-blow) thermomagnetic tripping.

How many poles does the 2800887 have?

2 poles.

What is the short-circuit switching capacity?

400A at 240VAC and 600A at 80VDC.

What is the degree of protection?

IP30 in the actuation area.