2800866 The Phoenix Contact 2800866 is a 1-position thermomagnetic device circuit breaker with a 12A rated current and 277V AC rated voltage. It features an F1 (fast-blow) tripping characteristic.
Mfr Part #:

2800866

Mfr Name: Phoenix Contact
Phoenix Contact
The Phoenix Contact 2800866 is a 1-position thermomagnetic device circuit breaker with a 12A rated current and 277V AC rated voltage. It features an F1 (fast-blow) tripping characteristic.
Stock on Request

2800866 Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Breaker Type
Color
Contact Type
Current Rating (Amps)
Design
Fuse Type
Height
Insulation Resistance
Mounting Type
Number of Poles
Number of Positions
Voltage Rating

2800866 Description

Short technical summary and product information.

The Phoenix Contact 2800866 is a single-pole thermomagnetic device circuit breaker designed for reliable circuit protection. It offers a rated current of 12A and a rated voltage of 277V AC (UL) or 240V AC (IEC), with DC voltage ratings up to 50V.

 

This breaker utilizes a thermomagnetic tripping method with an F1 (fast-blow) characteristic, ensuring quick response to overcurrents. It includes a 1 PDT contact for signaling purposes and a trip-free mechanism for enhanced safety. The compact design and plug-in housing concept allow for modular expansion and integration with CLIPLINE complete accessories.

 

Installation is on a base element, and the device has dimensions of 45mm height, 12.3mm width, and 52mm depth. It operates within an ambient temperature range of -30°C to 60°C and has an IP30 degree of protection for the actuation area. The breaker is constructed with an insulating material group II and meets UL 94 V0 flammability standards.

2800866 Quick Information

Product Type: Circuit Breaker
Series: F1
Canonical Name: Phoenix Contact CB TM1 12A F1 Thermomagnetic Device Circuit Breaker
Subcategory: Thermomagnetic

2800866 Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

2800866 Features

  • Thermomagnetic tripping with F1 characteristic.
  • 12A rated current at 277V AC.
  • Compact design with modular housing.
  • 1 PDT auxiliary contact for signaling.
  • Operates from -30°C to 60°C.

2800866 Applications

  • Protects electrical circuits from overloads.
  • Suitable for modular system integration.
  • Enables remote monitoring via signaling.
  • Used in industrial control panels.
  • Provides fast-acting fault interruption.

2800866 FAQs

7 frequently asked questions generated from this part’s specifications.
What is the rated operating voltage?

240 V AC (IEC 60934), 277 V AC (UL 1077, UL 508 with plug-in base), and 50 V DC (IEC/UL).

What is the package or mounting type?

Mounts on a base element. Module dimensions: 45 x 12.3 x 52 mm (single), complete module: 90 x 12.3 x 77.3 mm.

What is the operating temperature range?

-30 °C to 60 °C (operation), -40 °C to 80 °C (storage/transport).

What is the short-circuit switching capacity?

300 A at 240 V AC, 600 A at 50 V DC.

What type of tripping mechanism does it have?

Thermomagnetic (TM) with trip-free (positive) mechanism.

What is the degree of protection?

IP30 on actuation area.

What are the auxiliary contact ratings?

277 V AC / 0.5 A (low-induction), 277 V AC / 1 A (low-induction, max 2000 cycles), 50 V DC / 1 A (low-induction).