| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Ambient Temperature | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating |
This E-T-A 2216-S110-P1M1-S111-A-10A is a single-pole, thermal-magnetic circuit breaker designed for reliable circuit protection. It offers a current rating of 10A and can handle voltages up to 240VAC or 50VDC.
The breaker utilizes a slide switch actuator for operation and is designed for holder mounting. It meets the requirements of EN 60934 (IEC 60934) standards, specifically S-type, TM.
Key electrical specifications include a characteristic curve of M1, with thermal tripping between 1.01-1.4x IN and magnetic tripping between 6-12x IN for AC, and 8-15x IN for DC. It also includes one changeover auxiliary contact.
Environmental considerations include an operating temperature range of -30°C to 60°C and a degree of protection of IP30 for the operating area. The interrupting capacity is 300A at 240VAC (1-pole) and 1500A at 32VDC (1-pole).
The current rating is 10A.
The voltage rating is 240VAC and 50VDC.
It uses a slide switch actuator.
The operating temperature range is -30°C to 60°C.
Yes, it has one changeover auxiliary contact.
The interrupting capacity is 300A at 240VAC and 600A at 50VDC.
The degree of protection is IP30.