The E-T-A 2216-S110-P1F1-S111-A-1A is a single-pole thermal magnetic circuit breaker designed for overcurrent protection. It features a compact plug-in mounting design and blade terminals.
Key electrical specifications include a current rating of 1A and a voltage rating of 240VAC or 50VDC (1-pole) / 80VDC (2-pole). The breaker utilizes a thermal-magnetic trip mechanism with an F1 characteristic curve. It also includes a change-over auxiliary contact.
This circuit breaker meets EN 60934 (IEC 60934) standards and is suitable for protecting AC and DC control circuits in automation technology, process control, power plants, infrastructure, marine, machine building, and rail engineering. It complies with relevant railway standards DIN EN 50155, DIN EN 61373, and EN 45545.
Environmental specifications include an operating temperature range of -30°C to 60°C and an IP30 degree of protection for the operating area. The device has undergone vibration, shock, corrosion, and humidity testing according to IEC standards.
AC 240V (1-pole), DC 50V (1-pole), DC 80V (2-pole).
1A continuous, with a range of 0.5-16A available.
300A at 240VAC (1-pole), 600A at 50VDC (1-pole) per IEC/EN 60934; 1000A at 277VAC per UL 1077.
-30 to 60°C.
Plug-in mounting with blade terminals.
Yes, 1 change-over auxiliary contact rated at 240VAC/0.5A (VDE) and 277VAC/0.5A (UL).
F1 curve: thermal trip 1.01-1.4 x IN, magnetic trip 2-4 x IN (for DC).