| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Ambient Temperature | |
| Breaker Type | |
| Current Rating (Amps) | |
| Illumination | |
| Insulation Resistance | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating |
This E-T-A 2216-S110-P1F1-S111-A-15A is a single-pole thermal magnetic circuit breaker designed for reliable overcurrent protection. It features a 15A current rating and can handle voltages up to 240VAC and 50VDC.
The breaker utilizes a slide switch actuator for operation and offers a characteristic curve F1. It includes one change-over auxiliary contact for signaling purposes. The device meets EN 60934 (IEC 60934) standards and is suitable for AC and DC control circuits in automation technology, process control, power plants, infrastructure, marine, machine building, and rail engineering.
With a compact design and plug-in mounting capability, it ensures easy installation and maintenance. The circuit breaker operates within an ambient temperature range of -30 to 60°C and provides a degree of protection IP30 for the operating area.
The breaker is rated for 240V AC (nominal) and 50V DC for 1-pole operation, or 80V DC for 2-pole operation.
The nominal current rating is 15A, with a range of 0.5-16A.
IEC interrupting capacity is 300A at 240V AC (1-pole) and 1500A at 32V DC (1-pole). UL 1077 interrupting capacity is 1000A at 277V AC, 1000A at 50V DC (1-pole), and 1000A at 80V DC (2-pole).
The breaker uses an F1 characteristic curve.
Yes, it includes one change-over auxiliary contact.
The ambient operating temperature range is -30°C to 60°C.
It uses holder mounting and is compatible with DIN rail systems.