The E-T-A 2-6400-IG8-L10-SI-6A is a single-pole thermal overcurrent circuit breaker conforming to EN 60934 (IEC 60934) standards. It utilizes a snap-action mechanism that is tease-free and trip-free, with a standard push-to-reset actuator.
This circuit breaker is rated for 250V AC and 28V DC, with a current rating of 6A. It offers a current rating range from 0.05A to 16A and features auxiliary contacts (1 N/C, 1 N/O). The interrupting capacity is up to 2000A at 250V AC, depending on the current rating.
Designed for panel mounting, it can be installed via a threadneck mechanism (3/8-27UNS-2A or M12x1 options) or as a standard panel mount. The operating temperature range is -20°C to 60°C. The degree of protection for the operating area is IP40, and for the terminal area is IP00.
Typical applications include motors, transformers, solenoids, and controls for oil and gas boilers. It is approved by CSA, IEC, and UL standards.
The voltage rating is 250V AC and 28V DC.
The current rating is 6A.
It supports panel mounting and threadneck mounting.
The operating temperature range is -20°C to 60°C.
Typical applications include motors, transformers, solenoids, and controls for oil and gas boilers.