| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Ambient Temperature | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Insulation Resistance | |
| Mounting Type | |
| Number of Poles | |
| Termination Style | |
| Voltage Rating |
The E-T-A 1658-G21-02-P10-055800-10A is a single-pole thermal overcurrent circuit breaker from the 1658 series. It offers a manual reset with a cycling trip-free mechanism and a cost-effective design meeting international requirements.
Key electrical specifications include a voltage rating of 240 VAC or 28 VDC and a current rating of 10 A. The breaker type is thermal, with an interrupting capacity of 200 A at 125 VAC or 32 VDC. It has a dielectric strength of 3000 V and an insulation resistance greater than 100 MΩ.
Designed for panel mounting with a push-to-reset actuator, this circuit breaker is suitable for typical applications such as battery chargers, consumer products, power supplies, and motors. It operates within an ambient temperature range of -20 to +60 °C.
The device meets various international standards, including UL, CSA, VDE, and EN 60934 (IEC 60934). It features blade terminals and a compact, lightweight design.
The circuit breaker has a voltage rating of 240 VAC and 28 VDC.
The current rating is 10 A.
It features a manual reset with a push-to-reset actuator.
The ambient temperature range is -20 to +60 °C, with a maximum of +40 °C for currents ≤ 7 A.
The interrupting capacity is 200 A at 125 VAC or 32 VDC.
It supports panel mounting.