The E-T-A 1658-A21-02-P10-15A is a single-pole, thermal overcurrent circuit breaker with a manual reset mechanism. It is designed for panel mounting and features blade terminals for connection.
This circuit breaker has a current rating of 15A and can operate at AC voltages up to 240V or DC voltages up to 28V. It offers an interrupting capacity of 200A at 8-30A and 2,000A under specific AC and DC conditions.
The operating temperature range for this device is -20°C to +60°C, with a reduced maximum ambient temperature of +40°C for current ratings up to 7A. It meets international requirements with no exposed metal parts that could become current-carrying.
Typical applications for this circuit breaker include battery chargers, consumer products, power supplies, and motors. It is approved by UL, CSA, VDE, and EN 60934 (IEC 60934).
240V AC and 28V DC.
-20°C to +60°C, derated to +40°C for current ratings ≤7A.
Panel mount with blade terminals.
15A.
Thermal circuit breaker with automatic reset.
200A for 8-30A, and 2,000A at 240VAC (5-16A) and 2,000A at 28VDC (5-30A).
1,000 operations at 2x rated current, inductive or resistive.