| Category | |
| Manufacturer Name | |
| Actuator Type | |
| Ambient Temperature | |
| Approval Agency | |
| Breaker Type | |
| Current Rating | |
| Current Rating (Amps) | |
| Illumination | |
| Illumination Voltage (Nominal) | |
| Insulation Resistance | |
| Mounting Type | |
| Number of Poles | |
| Voltage Rating |
The E-T-A 1410-F110-P1F1-W19QE3-1A is a miniaturized, single-pole thermal overcurrent circuit breaker designed for ON/OFF switching and fast overload protection. It combines switching and protection in a single component, conforming to S-type TO CBE standards (EN 60934/IEC 60934).
This circuit breaker has a voltage rating of 250V AC and 48V DC (UL/CSA), with specific ratings for DC voltages up to 60V. The current rating is 1A. It features a rocker actuator with a rounded profile and is designed for panel mounting, fitting a cut-out of 28 x 12.7 mm.
Under overload conditions, an internal neon indicator illuminates to signal a tripped status, providing a clear visual cue of the power interruption cause. Resetting is achieved by returning the rocker switch through the OFF position and back ON. The device is largely temperature-insensitive and operates within an ambient temperature range of -40 to +70 °C.
Key specifications include an interrupting capacity of 2000A at 250V AC (UL 1077) and 200A at 48V/60V DC. It offers a typical circuit life of 30,000 operations for currents up to 6.3A. The operating area has an IP30 degree of protection.
The voltage rating is 250V AC, with additional ratings of 48V DC (UL/CSA) and 60V DC (UL).
The current rating is 1A.
This circuit breaker is designed for panel mounting.
The ambient temperature range is -40 to +70 °C.
Yes, it features green illumination with a nominal voltage of 140V.