1180-02-6A The E-T-A 1180-02-6A is a thermal circuit breaker designed for AC and DC voltage applications. It features a compact 8.2 mm width and a push-push actuator for easy operation.
Mfr Part #:

1180-02-6A

Mfr Name: ETA
ETA
The E-T-A 1180-02-6A is a thermal circuit breaker designed for AC and DC voltage applications. It features a compact 8.2 mm width and a push-push actuator for easy operation.
Stock on Request

1180-02-6A Specifications Quick View

Most important parameters for selection – full specs in datasheet.
Category
Manufacturer Name
Actuator Type
Ambient Temperature
Breaker Type
Current Rating
Current Rating (Amps)
Illumination
Mounting Type
Number of Poles
Voltage Rating
Width

1180-02-6A Description

Short technical summary and product information.

The E-T-A 1180-02-6A is a compact thermal circuit breaker designed as a replacement for conventional fuses in AC and DC voltage systems. It offers reliable switching behavior with a snap-action, positively trip-free mechanism. The push-push button allows for direct load switching for maintenance purposes, preventing device loss as it remains within the terminal block.

 

This circuit breaker is suitable for standard terminal blocks and DIN rail mounting, making installation easy. It features a fine grading of current ratings and is universally applicable for AC and DC circuits. The compact design saves space and weight in equipment. It meets the requirements of the EN 60934 (IEC 60934) circuit breaker standard.

 

Key specifications include a 6A current rating, 250V AC voltage rating, and 72V DC rated voltage. The operating temperature range is -20 to 60 °C. Typical life is rated at 6,000 operations at 1x In (low-inductance) or 3,000 operations at 1x In (inductive).

1180-02-6A Quick Information

Product Type: Circuit Breaker
Series: 1180
Canonical Name: E-T-A 1180-02-6A Thermal Overcurrent Circuit Breaker
Subcategory: Thermal Overcurrent Circuit Breaker

1180-02-6A Compliance

RoHS Status: RoHS Compliant
Moisture Sensitivity Level (MSL): 1 Unlimited
REACH Status: REACH Unaffected

1180-02-6A Features

  • Compact thermal circuit breaker design saves space.
  • Push-push actuator for easy load switching.
  • Suitable for AC and DC voltage applications.
  • Designed for DIN rail mounting.
  • Meets EN 60934 (IEC 60934) standard.

1180-02-6A Applications

  • Protection of loads in power distribution.
  • Used in control cabinets.
  • Suitable for process control systems.
  • Replacement for conventional fuses.

1180-02-6A FAQs

7 frequently asked questions generated from this part’s specifications.
What is the voltage rating of the 1180-02-6A?

250VAC and 72VDC.

What is the operating temperature range?

-20 to 60°C.

What is the mounting type?

Holder mount.

What is the current rating?

6A.

What is the actuator type?

Push-push.

How many poles does it have?

1.

What is the typical life expectancy?

6000 operations at 1xIn low-inductance, 3000 at 1xIn inductive, 500 at 2xIn inductive.